WADECO Solids Flow Detector
The MWS-DP-3 Microwave Solids Flow Sensor detects moving solids utilizing
microwave high penetrability and the Doppler effect. The sensing head
transmits microwaves toward the target material. A portion of the
microwaves are reflected back to the sensing head and analyzed as to whether
they are from a moving or stationary object. The highly-penetrable
microwave passes through a buildup on the head and even through pipe made of
non-conducting materials such as plastics. The unit is best suited for
detecting such materials as powders, granules, etc, moving through a vacuum
pipeline.
Microwave Solids Flow Sensor (MWS-DP-3)GENERAL
| |
When microwaves transmitted through the air encounter an object, some will be
reflected, some absorbed and the rest will pass through the object.
The amount of microwaves that pass through the object depends on the composition
of the object encountered.
Generally speaking, microwaves cannot penetrate metals and are reflected; water
absorbs the most microwaves.
Microwaves can easily pass through plastics, glass, ceramic, paper, etc.
On the other hand, when microwaves are transmitted and reflected back to the
sensor from a moving object, a frequency shift is generated between the
transmitted and the reflected waves by means of the Doppler effect, which is
converted to a motion signal and actuates an output relay. |
 |
|
SPECIAL FEATURES
- HIGH PENETRATION
- Easily penetrates process buildup on antenna, firebrick, refractory,
etc.
- The sensor can be installed on the exterior of a plastic or ceramic
pipe and detect the flow of material within the pipe.
- NON-INTRUSIVE INSTALLATION
- Mounted flush, no intrusion or damage
to material flow.
- EQUIPPED WITH A FILTER FOR SCREENING
UNNECESSARY INCOMING DOPPLER SIGNALS
- This function eliminates unnecessary
incoming Doppler signals such as, signals from a vibrating pipe or
conveyor and improves the signal to noise ratio.
- This enables the sensor to be used in
places where previously, non-contact flow detection was hardly possible
- EQUIPPED WITH A SENSITIVITY MARGIN
INDICATOR
- The received power level and the
sensitivity set point are indicated on the sensor allowing for easy
visual adjustment and maintenance of the sensor.
- The indicator clearly displays the
advantage of the filter screening effect.
- SELECTABLE DETECTION MODE
- Either flow or non-flow detection mode may be selected.
- EQUIPPED WITH A TEST BUTTON
- LED indicators indicate microwave circuit status and internal
temperature when the test button is pushed.
- EQUIPPED WITH A DOPPLER SIGNAL INCOMING INDICATOR
- An LED indicator turns on when the Doppler signal is received.
Flow and non-flow conditions are clearly displayed.
SWITCHES AND INDICATORS